NX-HTC4505-5
8 loops, Thermocouple/Pt100/Analog input, 8 Voltage outputs (for driving SSR), Heat or Cool control, Heater burnout alarm, MIL connector
Specificaties
I/O system | NX I/O Bus |
Type of module | Temperature control |
Number of digital inputs | 0 |
Digital input type | None |
Number of digital outputs | 8 |
Digital output type | PNP, PWM |
Number of analog inputs | 8 |
Temperature input type | B, C (WRe5-26), E, J, JPt100, K, L, N, P (PLII), Pt100, R, S, T, U |
Number of control loops | 8 |
Linear analog input type | 0 to 10 V, 0 to 20 mA, 0 to 5 V, 1 to 5 V, 4 to 20 mA |
Input circuit type | Isolated |
Number of analog outputs | 0 |
Linear analog output type | None |
Conversion time | 50 ms/unit |
Signal processing | Free running |
Control function | Heat or cool |
Heater burnout detection | |
IO-Link master | |
I/O connection type | MIL (plug not included) |
Number of I/O connectors | 2 |
Detachable I/O connector | |
Suitable for safety functions | |
SIL according to IEC 61508 | None |
Degree of protection (IP) | IP20 |
Product Height (unpacked) | 106 mm |
Product Width (unpacked) | 32.1 mm |
Product Depth (unpacked) | 89.8 mm |
Product Weight (unpacked) | 0 g |
Accessoires
E54-CT1 | Stroomtrafo, tot 50 A, gat: 5,8 mm, bodemmontage, soldeeraansluiting |
|
|
E54-CT3 | Stroomtrafo, tot 120 A, gat: 12 mm, montage M3 schroeven, soldeeraansluiting |
|
|
XW2K-34G-T | Interfacebedradingssysteem voor algemeen gebruik met push-in plus-technologie, 34-punts MIL-connector, ingang/uitgang, 1 A, NPN/PNP, 125 VAC, 30 VDC, DIN-rail horizontale en verticale montage |
|
|
XW2Z-050EE | Parallelle I/O afgeschermde kabel voor FH controller 50 cm, te gebruik in combinatie met XW2B-34G_ |
|
|
XW2Z-100EE | Parallelle I/O afgeschermde kabel voor FH controller 1 m, te gebruik in combinatie met XW2B-34G_ |
|
|
XW2Z-200EE | Parallelle I/O afgeschermde kabel voor FH controller 2 m, te gebruik in combinatie met XW2B-34G_ |
|
Reserveonderdelen
NX-AUX03 | Koudeverbindingssensor alleen voor NX-HTC |
|